2 optional power exhaust or gravity, Exhaust hood - cabinets a, b, c, Figure 16a - attaching optional exhaust hood(s) – Reznor RECC Unit Installation Manual User Manual
Page 31: Figure 16b - optional power exhaust dimensions, This side is attached to the maps, Cabinet at the factory .)

Form I-MAPSIII&IV, P/N 222917R9, Page 31
6.2 Optional Power
Exhaust or
Gravity Exhaust
Hood on MAPS
®
Cabinets A, B,
C (without an
energy recovery
module)
If ordered with Option PE, the system is factory equipped with a power exhaust for
building air. The power exhaust blower, motor, and damper are assembled and at the
factory. The power exhaust hood(s) is factory assembled and shipped in a separate
carton to be installed at the site. To attach, slide the hood(s) over the flange and fasten
with the sheetmetal screws provided.
NOTE: Attach the power exhaust hood BEFORE
installing the outside air hood or horizontal discharge ductwork.
Side View of Option PE Power Exhaust
Cabinet and field attached Hood
Factory-
Installed
Power
Exhaust -
Cabinets
A, B, & C
Field-
Installed
Hood
Depending on the size of the
unit, one or two hoods with
sheetmetal screws are shipped
in separate cartons.
Slide the hood over the flange
and attach across the top and
on each side.
Attach the hood(s) BEFORE
installing an outside airhood
or horizontal ductwork.
Power
Exhaust
Hood
FIGURE 16A - Attaching
Optional Exhaust
Hood(s)
NOTE: Power exhaust
hood is illustrated. Follow
same procedure for gravity
exhaust hood.
Cabinet A and B sizes (see Cross Reference, pages 71-72) have a 9x10 exhaust
blower, gravity damper, and one shipped-separate hood. Cabinet C sizes have dual
9x10 blowers, gravity dampers, and two shipped-separate hoods. Check the rating
plate for motor size (1/2 - 5 HP).
Standard control would turn the exhaust blower on when the unit blower runs. If
optional return air dampers are ordered, the power exhaust is wired to coordinate with
the appropriate damper position.
Side View of Option PE, Power Exhaust Cabinet and
Hood - Applies to MAPS Cabinet Sizes A, B, and C
Exhaust
Airflow
12-3/4
(324mm)
12-3/8
(314mm)
25-1/8 (638mm)
17-7/8
(454mm)
4-1/2 (114mm)
Top View
of Power
Exhaust
Cabinet -
MAPS
Cabinets
A and B
Exhaust
Airflow
Cab
A
= 21-13/16 (554mm)
Cab B = 22-13/16 (579mm)
14-15/16 (379mm)
CabA = 5-7/16 (138mm)
Cab B = 20-3/8 (518 mm)
Cabinet
A
= 42-3/16 (1072mm)
Cabinet B = 57-1/8 (1451mm)
Top View
of Power
Exhaust
Cabinet -
MAPS
Cabinet C
Exhaust
Airflow
Exhaust
Airflow
14-1/2 (368mm)
14-1/2 (368mm)
7
(178mm)
25-13/16 (554mm)
36 (914mm)
68-3/4 (1746mm)
6-15/16
(176mm)
Attach hood(s) with screws provided. Install hood(s)
before attaching horizontal ductwork or outside air hood.
NOTE: Cabinets A & B - the power exhaust cabinet
extends 1-3/4 (44mm) below the MAPS cabinet.
Hood
(shipped in
a separate
carton)
Hood
(shipped in
a separate
carton)
Hood
(shipped in
a separate
carton)
FIGURE 16B -
Optional Power
Exhaust Dimensions
(This side is attached to the MAPS
®
cabinet at the factory
.)
(This side is attached to the MAPS
®
cabinet at the factory
.)
RPM/HP Table - Power Exhaust Option PE1 on Cabinet A & PE2 on Cabinet B
CFM
External Static Pressure (ESP)
0.3
0.5
0.8
1.0
1.5
500
650/.50
--
--
--
--
1000
870/.50
1040/.50
1200/.50
1325/.50
1500/.75
1500
940/.50
1100/.50
1240/.75
1370/.75
1600/1.00
2000
1050/.75
1190/1.00 1310/1.00 1430/1.50 1640/1.50
2500
1190/1.50 1300/1.50 1410/1.50 1510/2.00 1710/2.00
3000
1350/2.00 1440/2.00 1535/3.00 1625/3.00 1800/3.00
3500
1520/3.00 1600/3.00 1680/5.00 1760/5.00
--
4000
1700/5.00 1760/5.00 1800/5.00
--
--
RPM/HP Table - Power Exhaust Option PE3 on Cabinet C
CFM
External Static Pressure (ESP)
0.3
0.5
0.8
1.0
1.5
1000
680/.50
--
--
--
--
1500
845/.50
1025/.50
1140/.50
--
--
2000
870/.50
1040/.75
1200/.75
1325/1.00
--
2500
900/.75
1070/.75
1220/1.00 1345/1.50 1575/1.50
3000
940/.75
1100/4.00 1240/1.50 1370/1.50 1600/2.00
3500
1000/1.00 1140/1.50 1275/1.50 1400/2.00 1620/3.00
4000
1050/1.50 1190/2.00 1310/2.00 1430/3.00 1640/3.00
4500
1120/2.00 1240/2.00 1360/3.00 1470/3.00 1675/5.00
5000
1190/3.00 1300/3.00 1410/3.00 1510/5.00 1710/5.00
5500
1270/3.00 1370/5.00 1470/5.00 1570/5.00 1750/5.00
6000
1350/5.00 1440/5.00 1535/5.00 1625/5.00
--
6500
1435/5.00 1520/5.00
--
--
--
- REDB Unit Installation Manual RECB Unit Installation Manual RDDC Unit Installation Manual RDCC Unit Installation Manual RDDB Unit Installation Manual RDCB Unit Installation Manual RDC Unit Installation Manual RCC Unit Installation Manual RDB Unit Installation Manual RCB Unit Installation Manual REDC Unit Installation Manual MAPSIV Unit Installation Manual MAPSIII Unit Installation Manual