Toshiba – Toshiba VF-SX User Manual
Page 92
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
TOSHIBA
10-5
The ON and OFF conditions of SSI, SS2/OOG, and SS3/EX switches and the selected
operation frequencies are as shown in Table 10-5.
TABLE 10-5: INPUT TERMINAL SELECTION TABLE
Input
Temlnal
Selection
Temlnal
Selected
Operation
Frequency
SS3/
EX
SS2/
JOG
SSI
0
: SS2
SS3
OFF
OFF
OFF
Operating frequency set by terminal
OFF
OFF
ON
1st speed run operation frequency
OFF
ON
OFF
2nd speed run operation frequency
OFF
ON
ON
3rd speed run operation frequency
ON
OFF
OFF
4th speed run operation frequency
ON
OFF
ON
5th speed run operation frequency
ON
ON
OFF
6th speed run operation frequency
ON
ON
ON
7th speed run operation frequency
/ : JOG
SS3
OFF
OFF
OFF
Operating frequency set by terminal
ON/OFF
ON
ON/OFF
Jogging run operation frequency
ON
OFF
ON
1st speed run operation frequency
ON
OFF
OFF
2nd speed run operation frequency
ON
OFF
ON
3rd speed run operation frequency
SS2
EX
OFF
OFF
OFF
Operating frequency set by terminal
OFF
OFF
ON
1st speed run operation frequency
OFF
ON
OFF
2nd speed run operation frequency
OFF
ON
ON
3rd speed run operation frequency
ON
ON/OFF
ON/OFF
Emergency stop
3
:
JOG
EX
OFF
OFF
OFF
Operating frequency set by terminal
OFF
ON
ON/OFF
Jogging run frequency
OFF
OFF
ON
1st speed run operation frequency
ON
ON/OFF
ON/OFF
Emergency stop