8 basic wiring recommendations, 8 basic wiring recommendations -7, Toshiba – Toshiba VF-SX User Manual

Page 26

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

5-7

Radio Freouencv Interference

During operation of the drive there may be noise generated by the drive in the
frequency range associated with radio transmission signals. This noise may
adversely affect sensitive electronic equipment near the drive. If this

condition persists install a RF/EMI (Radio Frequency or Electromagnetic

Interference) filter on the input to the drive. Shield the motor leads in

metallic conduit. These steps will reduce radio frequency interference.

Contact Toshiba for details, or see Chapter 15.

WARWIH6:
Do not operate or energize the inverter before checking between the motor and the

inverter for mis-wiring or short circuits in the motor. Do not operate the drive
if the motor is shorted. Do not ground the neutral point of the motor star­

winding.

5.8 Basic Wiring Recommendations

TABLE 5-1: BASIC WIRING RECOHMENOATIONS

DRIVE MODEL VFSX- 2001UP 2002UP 2004UP 2007UP 2015UP12022UP12037UP1 1

KW RATING

0.1

0.2

0.4

0.75

1.5

2.2

3.7 1

HP RATING

1/8

1/4

1/2

1

2

3

5 j

MCCB SIZE

5 A

5 A

5 A

10 A

15 A

20 A

30 A 1

HC AMPS (1)

12 A

12 A

12 A

12 A

12 A

12 A

18 A 1

OL RELAY RATING

0.7 A

1.3 A

2.3 A

4.2 A

6.6 A

9.3 A

15 A 1

POWER WIRE SIZE

12 GA

12 GA

12 GA

12 GA

12 GA

12 GA

10 GA 1

CONTROL WIRE SIZE 18 GA

18 GA

18 GA

18 GA

18 GA

18 GA

18 GA 1

WIRE SIZE FOR

REGENERATIVE

BRAKING RESISTOR

N/A

N/A

14 GA

14 GA

12 GA

12 GA

12 GA 1

NOTES:

1

.

2

.

3.

4.

Always use a surge suppression device on the coil of the MC contactor.

Use shielded cable on control circuits. See Figure 5.2.
Use 10 gauge wire or larger for ground circuit.

Power wire sizes in table above are minimum size. For cable lengths over

100 feet, or where voltage drops may cause application problems, larger

wire may be required.