11-8
TOSHIBA
ST
cc
SS1 SS3
(EX)
h o h o h
F R ST
Switch Switch Switch
EX
Switch
Figure 11.2 Forward, Reverse, and Emergency Stop
Switches
11.3.3
Emergency DC Injection Braking
Stop Controi Time [f c/b t]
When
[E 5 t P]
-
P,
(emergency DC injection braking stop is selected) and DC
injection braking is not retired during normal stop, set the DC injection
braking time to [
d b t ]
.
0 .
See Section 11.2 in this Chapter for instructions to set parameters [
d b U ]
and
[ d b t } .
11.4 Retry [ r t r y ]
The retry function allows the drive to perform an auto-restart, when this feature
is desirable and applicable. The retry feature operates after a protective
function or parameter trips the drive.
CAUTION:
Before using the retry function confirm that there will be no problems with
the load or application when an automatic restart occurs. Certain large
inertia loads, or loads requiring large torque boost to start may not work
properly with the retry feature. Also, personnel safety is an obvious
consideration.