9-8
TOSHIBA
9.1.4
V/f Patterns
[P tj
The V/f characteristic may be set for constant torque loads, resulting in a
linear relationship between output voltage and frequency. There is a separate
setting for variable torque loads which sometimes results in energy savings, if
the application is suitable for this V/f pattern. Fans and centrifugal pumps are
the most common types of loads associated with the variable torque load V/f
pattern. See Figures 9.4 and 9.5.
TABLE 9-3: SELECTION OF CONSTANT OR VARIABLE TORQUE V/f PATTERNS
1 [P t]
Value
Function
0
For constant torque characteristics.
/
For variable torque characteristics (Energy saving
operation is possible. Motor noise may also be
decreased.)
Pt-0:
Constant
Torque
Characteristics
P
fc - / : Variable Torque
Characteristics
Output
Voltage
Output
Voltage
Figure 9.4 Constant Torque
V/f Curve
Figure 9.5 Variable Torque
V/f Curve