Do not touch any of the terminal blocks or any of the circuitry inside the

drive while the "CHARGE" LED Indicator is illuminated. An electrical

charge is maintained on the capacitor and other electrical components

while this lamp is lit. Treat this condition with respect.

Not all motors can be driven to speeds above the base frequency (50 HZ or
60 HZ) for which they are designed. The variable speed range should be

limited to a safe operating range, since any general purpose motor that

can be driven by the inverter is actually designed for constant speed
operation. At operation above 60 HZ with a general purpose motor expect

limits on bearing life, mechanical strength, vibration, noise, and other

motor design variables to affect operation. In general, only apply the

inverter within the guidelines shown in Table 9-1. Consult the motor

manufacturer for recommendations for motor operation beyond these
guidelines.

TABLE 9-1: MAXIMUM PERMISSIBLE MOTOR SPEEDS

Motor Frame Number

Permissible Haxiimai Frequency (HZ)

Number of Poles

2

4

6

42T

60

120

_

48T

_

56T

120

140T

180T

210T