10-14

TOSHIBA

The following example shows a setting to use a 0 - 50 Hz output frequency

characteristic for a 4-20mA input signal. This can be set by selecting "1" in
the drive nx)de.

Input signal point 1

[P

/ 1

20%

Point 1 output frequency rP“P / ]

0 HZ

Input signal point 2 [Pel

100%

Point 2 output frequency [

P-PP]

50 HZ

Hz

QV 4mA

20mADc J1=5V, J2="V

Figure 10.7 Frequency Setting Signal

Characteristics at 50 Hz

* Separate point 1 and 2 by at least 10%. The [

E ( ~ C . I

] diagnostic will

illuminate on the LED display when point 1 and point 2 are not separated

by at least 10%.

10.9 Jogging Run via Remote Control

[J 0 G],

[

J 5 t P]

The jogging run feature is used to operate the motor slowly, or for very brief

intervals. When the jogging run signal is received at terminal "JOG" the jogging

run frequency will be output immediately regardless of the set acceleration time.

The jogging run frequency [

J O G

] can be set between 0 and 20 HZ. When the

jogging run frequency is set to a value other than 0, selection of the jogging

stop pattern

[ J S E P ]

is enabled. See Table 10-11 for stopping options when

the OOG feature is enabled.