TOSHIBA

11-9

TABLE n-4:

RETRY PARAMETERS

[ r t r i / ] Value

Function

0

OFF (The trip status is protected, and

automatic start does not occur when the

inverter trips.)

/

ON (Automatic restart occurs when the

inverter trips under the proper

conditions.)

When the retry function is selected, the Inverter will automatically restart when
the power Is restored after a momentary power interruption or during faults due
to overcurrent, overvoltage, or overload.

The fault Indication and retry procedure are shown in Table 11-5.

TABLE 11-5: FAULT INDICATION AND RETRY PROCESS

1 Fault Indication

Retry Process

Stop Conditions

Momentary Power

Restarts continuously up

If a trip other than

Interruption

to 5 times.

overcurrent, overvoltage, or

overload occurs during retry.

Overcurrent

1st time: approximately
2 seconds after fault

OR

OR

occurrence

if a momentary power outage

2nd time: approximately

occurs again.

Overvoltage

2 seconds after 1st
retry.

OR

OR

3rd time: approximately
4 seconds after 2nd

if the restart is not

Overload

retry.

4th time: approximately

8 seconds after 3rd

retry,

5th time: approximately

15 seconds after 4th

retry.

possible all five times.