Toshiba 11-9 – Toshiba VF-SX User Manual
Page 116
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
TOSHIBA
11-9
TABLE n-4:
RETRY PARAMETERS
[ r t r i / ] Value
Function
0
OFF (The trip status is protected, and
automatic start does not occur when the
inverter trips.)
/
ON (Automatic restart occurs when the
inverter trips under the proper
conditions.)
When the retry function is selected, the Inverter will automatically restart when
the power Is restored after a momentary power interruption or during faults due
to overcurrent, overvoltage, or overload.
The fault Indication and retry procedure are shown in Table 11-5.
TABLE 11-5: FAULT INDICATION AND RETRY PROCESS
1 Fault Indication
Retry Process
Stop Conditions
Momentary Power
Restarts continuously up
If a trip other than
Interruption
to 5 times.
overcurrent, overvoltage, or
overload occurs during retry.
Overcurrent
1st time: approximately
2 seconds after fault
OR
OR
occurrence
if a momentary power outage
2nd time: approximately
occurs again.
Overvoltage
2 seconds after 1st
retry.
OR
OR
3rd time: approximately
4 seconds after 2nd
if the restart is not
Overload
retry.
4th time: approximately
8 seconds after 3rd
retry,
5th time: approximately
15 seconds after 4th
retry.
possible all five times.