CAUTION:
The Emergency Stop command Is a command to forcibly stop the operation by
depressing the Inverter unit keys on the touchpad when the drive Is not
controlled from the touchpad. This cannot be prohibited by any setting of
the Command Mode. The emergency stop will be regarded as a trip and will
be registered as a past error In the trip history section of the drive
memory.____________________________________________________________________
8.5 Starting the Drive from the Touchpad
After confirming all wiring Is connected to the proper terminals, the Inverter
may be operated using factory default settings, via the touchpad. This Is the
most simple mode of operation for the Inverter. This can serve as a simple test
for the Inverter/load combination. (See Chapter 6 for a brief look at the most
simple methods of control and power wiring for the drive.)
The factory default settings for all parameters are shown In Chapter 7.
It Is recommended to start the Initial run at a low frequency/speed for any test
operation.
Table 8-5 shows the touchpad keystroke sequency for starting the drive.