1. No-load Current Setting

The parameter [ CUrO] of the

[Or.C C]

group Is set by default to the

standard value, lOX. Additional adjustment is generally not required. However,

In the following cases adjustment of this parameter may be effective.

1.

If an over-excited state occurs during low voltage output (when the output

frequency is low), slightly increase [

CUrO

]. If the torque is not

quite sufficient, lower this parameter slightly. The starting point of

the voltage can be adjusted with the torque boost setting value (parameter

[Ub

]

in family

[G f~. F ].)

This parameter regulates the lower limit

of the automatic torque boost function.

2.

This parameter is also used as the setting data of the no-load current in

the slip frequency compensation function. When this parameter Is changed,

the setting data for the no-load current in slip frequency compensation
function will also be changed.

3.

The value will not always be the same as the no-load current value noted

on

the applicable motor data sheet or rating nameplate.

2. Torque Boost Maximum Value Setting

The maximum value of the automatic adjustment range is set by the parameter

[ U b H ]

of the

¡ O r . C C ]

group. The standard default value is

6 % .

The minimum value of the automatic adjustment at low frequencies is the torque

boost setting value [Ub ] of the fundamental group

[0 f~. F].

The standard

default setting for parameter

[ U b ]

is

3%.

If the automatic torque boost setting [UbH] is set lower than the initial

starting torque boost [Ub ], then the automatic torque boost is not active at

any output frequency, and the starting torque boost is the only boost present,

and only at lower speeds.