If a fault occurs due to an abnormally high power voltage or element error in the

inverter and a current flows constantly to the resistor, the thermal fuse in the

braking resistor circuit will blow. In this case it is not uncoiimion for a small
amount of smoke to arise from the resistor, and the resistor surface temperature

may be extremely high. Do not install the resistor directly onto any flammable

surface or subpanel.

CAUTION:

When using a braking resistor other than the standard unit, install an

input contactor or a main circuit breaker with a shunt trip on the inverter
incoming power. Electrically interlock this device so that the power

circuit will open with the operation of the fault relay (FL) in the

inverter or an external overload relay.

TABLE 11-1: SETTINB OF THE REGENERATIVE DISCHARGE RESISTOR PROTECTION PARANETER

[ P b ]

Value

Function

0

Regenerative Discharge Braking not engaged.

/

Regenerative Discharge Brake engaged, no braking resistor

overload detection (when an VERY large resistor is used).

г

Regenerative discharge brake engaged, braking resistor

overload detection is ON (when the standard size resistor

is used).

The overvoltage stall operation refers a voltage increase on the DC bus during

deceleration. This DC voltage rise can be automatically limited to prevent

tripping on overvoltage. Thus, the deceleration time may be longer than the set

deceleration time.

TABLE 11-2: SETTING OF THE OVERVOLTAGE STALL PARAMETER

(OP 5 5]

Value

Function

0

Overvoltage stall operates. (This setting

is ignored

if [ P b ]

is / or

P.)

/

No overvoltage stall operation.