Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

12-11

1. No-Load Current Setting

The parameter [

C U r O

] of group

[ C f ~ . C

C] can be set at the standard

default value of lOX for most applications. Additional adjustment is generally

not necessary. However, in the following cases adjustment of this parameter may
be effective.

1.

This parameter will affect the slip compensation starting point. When the

value of [

C U r O ]

is increased, the value of the output torque when

compensation begins will increase slightly.

2.

This parameter is also used as the setting data of the no-load current in

automatic torque boost function. When this parameter is changed, the
setting data for the no-load current in automatic torque boost function

will also change.

3.

The value will not always be the same as the no-load current value noted
on the application motor data sheet or rating nameplate.

2. Motor Rating Slip Frequency

The rated slip frequency is defined by the motor data available on the nameplate

or motor data sheet. Refer to this data when setting parameter

[S F (~

]

EXAHPLF:

Set slip frequency compensation for a 1 HP motor, 230 volts, 60 HZ rated. The

motor nameplate states that the rated speed is 1710 RPH. (Synchronous speed is

1800 RPH)

Rated Slip Frequency

ISvnchronous Sneed - Rated Soeedl

Synchronous Speed

11800 - 17101 X 60

1800

X Output Frequency

- 3 HZ; (Set parameter [

5 F f”

] to

3)