TABLE 7-3: PARAMETER GROUP [

Cr.f] -

FUNDAMENTAL PARAMETERS

Function

Title

Adjustaent

Range

Unit

Shlp-

aent

User

Setting

Page

Koxiaua Frequency

F H

30 -- 240

0.1 KZ

80

9-4

Bate Frequency

u L

25 — 240

0.1 KZ

60

9-5

Torque Boost

u b

0 — 30

IX

3

9-7

V/f Pattern

P t

0: Constant Torque

1: Variable Torque

0

9-8

Upper Liait Frequency

U L

0.5 — Naxiaua Frequency

0.1 HZ

80

9-9

Lower Liait Frequency

L L

0 -- Upper Halt Frequency

0.1 HZ

0

9-9

Forward/Reverse Run

Selection

F r

0: Reverse Run

1: Forward Rtn

1

9-10

Acceleration Tiae 1

R C C l

0.1 - 3600

0.1 Sec

10

9-14

Deceleration TIae 1

d E C I

0.1 - 3600

0.1 Sec

10

9-14

Acc./Dec. 1 Pattern

P E 1

0: Linear

1: S-Character 1

2: S'Character 2

0

9-15

Acceleration Tiae 2

R C C P

0.1 - 3600

0.1 Sec

10

9-14

Deceleration Tiae 2

d E C P

0.1 - 3600

0.1 Sec

10

9-14

Acc./Dec. 2 Pattern

P E E

0: Linear

1: $-Character 1

2: S'Character 2

1

9-15 1

Acc./Dec. 1 or 2
Selection

R d E

0: Acceleratlon/Deceleration 1

1: Acceleratlon/Deceleration 2

2: Changeover of Acc./Dec.

Pattern 1 or 2

0

9-17

Frequency for

Switching Between

Acc./Dec. 1 and 2 <*)

R d E F

0 -- Kaxiaui Frequency

0.1 NZ

0

9-17

Drive Mode Selection

E U P

0: No Input Is Envied

1: General Purpose 50 NZ

Settings

2; General Purpose 60 M2

Settings

3: Standard Default Value

Settings

4: Clear Past Errors

<•*)

9-19

The parameters marked with an asterisk (*) wi11 be displayed as detailed parameters
only when the parameter in the row imnediately above this function is selected for
adjustment or review.

(**)

(**) "0" is always displayed for this parameter