9.3.2 Operation Using External Signals

FORWARD RUN AND REVERSE RUN:

These operations are avalTafale using renrate signals, as well as from the

touchpad. To perform these operations using remote signals, wire the correct
drive input terminal blocks as shown in Figure 9.8.

1.

Forward run and reverse run are
possible when either F or R is

ON and ST is shorted to CC. If

the signal from F-CC or R-CC is
opened the drive will decelerate
to

stop,

based

on

the

deceleration parameters

[d E C I ] or [d E C E],

Coasting stop is NOT available

if ST is shorted to CC. Remove

the factory installed jumper

between terminals ST and CC if
coasting stop is preferred over

decelerating stop. Simplified
wiring for this procedure is

shown in Chapter 6, Figure 6.2,

2.

Install the switches as shown in

Figure 9.8.

3.

Input the frequency setting signal to the correct terminals.

©

ST

©

CC

j

!^____

Figure 9.8 Installation of

Forward/Reverse Contacts

TABLE 9-5. FORWARD/REVERSE TERMINAL INPUT AND OPERATION

Terminal

Operation

ST-CC

F-CC

R-CC

OFF

ON/OFF

ON/OFF

Output OFF, Coasting Stop

ON

OFF

OFF

Stop

ON

OFF

ON

Reverse Run

ON

ON

OFF

Forward Run

ON

ON

ON

Reverse Run