TABLE 11-7: ELECTRONIC PROTECTION PARAMETERS

[ 0 L H ]

Value

Function

0

standard motor, without stall capability.

1

standard motor, with stall capability.

S

VF motor, without stall capability. I

3

VF motor, with stall capability. 1

Explanation of the soft-stall function:

If the inverter detects an overload, the output frequency and voltage are

automatically lowered before overload tripping can occur. Operation continues

without tripping at the frequency where the load current is balanced. This

parameter is typically applicable to variable torque type loads such as fans,

pumps, and blowers, etc. where the load current decreases when the operation
speed decreases.

CAUTION:

Do not apply the stall function to constant torque characteristic loads

_^^anyloadj|nth_^^£onstaTit_J^a£_cutxent_j^e2ardless_o^^

Electronic Thermal

Operation Level

Output Frequency

Figure 11.4 Standard Motor

Electronic Thermal Operation

Characteristics

Electronic Thermal

Operation Level

Maximum

Frequency

Output Frequency

Figure 11.5 VF Motor Electronic

Thermal Operation Characteristics