relay can only accomplish this if the relay has been added to the cooling tower temperature

controller. The

TOWER FAN RELAY

is turned on whenever the

CONDENSER WATER PUMP

is running, flow is verified, and the difference between cooler and condenser pressure is more

than 45 psid (310 kPad) (30 psid [207 kPad] for HFC-134a) or entering condenser water

temperature is greater than 85 F (29 C). The

TOWER FAN RELAY

is deenergized when the

condenser pump is off, flow is lost, the evaporator refrigerant temperature is less than the

override temperature, or the differential pressure is less than 40 psid (279 kPad) (28 psid [193

kPad] for HFC-134a) and entering condensing water is less than 80 F (27 C).

IMPORTANT: A field-supplied water temperature control system for condenser water

should be installed. The system should maintain the leaving condenser water tempera-

ture at a temperature that is 20° F (11° C) above the leaving chilled water temperature.

CAUTION

CAUTION

!

The tower-fan relay control is not a substitute for a condenser water temperature
control. When used with a Water Temperature Control system, the tower fan
relay control can be used to help prevent low condenser water temperatures.