beautypg.com

Extended shutdown, After extended shutdown – Carrier 19XL User Manual

Page 181

background image

Extended Shutdown

The refrigerant should be transferred into the storage vessel (if supplied; see

Pumpout and

Refrigerant Transfer Procedures

) in order to reduce machine pressure and possibility of leaks.

Maintain a holding charge of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant to prevent air from leaking

into the machine.

If freezing temperatures are likely to occur in the machine area, drain the chilled water,

condenser water, and the pumpout condenser water circuits to avoid freeze-up. Keep the

waterbox drains open.

Leave the oil charge in the machine with the oil heater and controls energized to maintain the

minimum oil reservoir temperature.

After Extended Shutdown

Be sure that the water system drains are closed. It may be advisable to flush the water

circuits to remove any soft rust which may have formed. This is a good time to brush the tubes if

necessary.

Check the cooler pressure on the LID default screen, and compare to the original holding

charge that was left in the machine. If (after adjusting for ambient temperature changes) any

loss in pressure is indicated, check for refrigerant leaks. See

Check Machine Tightness

section.

Recharge the machine by transferring refrigerant from the storage tank (if supplied). Follow

the

Pumpout and Refrigerant Transfer Procedures

section. Observe freeze-up precautions.