beautypg.com

To stop the machine, After limited shutdown – Carrier 19XL User Manual

Page 180

background image

based on load rate or temperature rate. It is accessed on the Equipment Configuration,

Config table (Table 2,

Example 5

).

To Stop the Machine

1. The occupancy schedule will start and stop the machine automatically once the time

schedule is set up.

2. By pressing the STOP button for one second, the alarm light will blink once to confirm that

the button has been pressed, then the compressor will follow the normal shutdown

sequence as described in the

Controls

section. The machine will not restart until the CCN or

LOCAL softkey is pressed. The machine is now in the OFF mode. If the machine fails to

stop, in addition to action that the PIC will initiate, the operator should close the guide vanes

by overriding the guide vane target to zero to reduce machine load; then by opening the

main disconnect. Do not attempt to stop the machine by opening an isolating knife switch.

High intensity arcing may occur.

Do not restart

the machine until the problem is diagnosed

and corrected.

After Limited Shutdown

No special preparations should be necessary. Follow the regular preliminary checks and

starting procedures.