Prepare the machine for start-up, To start the machine, Check the running system – Carrier 19XL User Manual

Page 178

background image

5. Protect the system from damage during shutdown periods.

6. Maintain the set point, time schedules, and other PIC functions.

Prepare the Machine for Start-Up

Follow the steps described in the

Initial Start-Up

section.

To Start the Machine

1. Start the water pumps, if they are not automatic.

2. On the LID default screen, press the LOCAL or CCN softkey to start the system. If the

machine is in the OCCUPIED mode, and the start timers have expired, the start sequence

will start. Follow the procedure described in the

Start-Up/Shutdown/Recycle

section.

Check the Running System

After the compressor starts, the operator should monitor the LID display and observe the

parameters for normal operating conditions:

1. The oil reservoir temperature should be above 140 F (60 C) during shutdown, and above

100 F (38 C) during compressor operation.

2. The bearing oil temperature accessed on the Status01 table should be 120 to 165 F (49 to

74 C). If the bearing temperature reads more than 180 F (83 C) with the oil pump running,

stop the machine and determine the cause of the high temperature.

Do not restart

the

machine until corrected.