Table 4 — Capacity Overrides

Override
Capacity
Control

First Stage Setpoint

Second
Stage
Setpoint

Override
Termination

View/
Modify
on LID
Screen

Default Value

Configurable Range

Value

Value

High
Condenser
Pressure

Equip-
ment
Service1

HCFC-22

HFC-134a

HCFC-22

HFC-134a

>

Override

Set Point
+ 4 psid
(28 kPad)

<

Override Set

Point

>

195 psig

(1345 kPa)

125 psig
(862 kPa)

150 to 245 psig
(1034-1689 kPa)

90 to 200 psig
(620 to
1379 kPa)

High Motor
Temperature

Equip-
ment
Service1

>

200 F

(93.3 C)

150 to 200 F
(66 to 93 C)

>

Override

Set Point
+10° F
(6° C)

<

Override Set

Point

Low
Refrigerant
Temperature
(Refrigerant
Override
Delta
Temperature)

Equip-
ment
Service1

<

3° F (1.6° C)

(Above Trippoint)

2° to 5° F
(1° to 3° C)

+ Override

T –1° F

(0.56° C)

>

Trippoint +

Override

T

+2° F (1.2° C)

High
Compressor
Lift (Surge
Prevention)

Equip-
ment
Service1

HCFC-22

HFC-134a

HCFC-22

HFC-134a

None

Within Lift
Limits Plus
Surge/ HGBP
Deadband
Setting

Min:
T1 — 1.5° F
(0.8° C)
P1 — 75 psid
(517 kPad)
Max:
T2 — 10° F
(5.6° C)
P2 — 170 psid
(1172 kPad)

Min:
T1 — 1.5° F
(0.8° C)
P1 — 50 psid
(345 kPad)
Max:
T2 — 10° F
(5.6° C)
P2 — 85 psid
(586 kPad)

0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to
1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to
1172 kPad)

0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to
1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to
1172 kPad)

Manual
Guide Vane
Target

Control
Algo-
rithm
Maint01

Automatic

0 to 100%

None

Release of
Manual
Control