Table 4, Capacity overrides, Table 4 — capacity overrides – Carrier 19XL User Manual
Page 270

Table 4 — Capacity Overrides
Override
Capacity
Control
First Stage Setpoint
Second
Stage
Setpoint
Override
Termination
View/
Modify
on LID
Screen
Default Value
Configurable Range
Value
Value
High
Condenser
Pressure
Equip-
ment
Service1
HCFC-22
HFC-134a
HCFC-22
HFC-134a
>
Override
Set Point
+ 4 psid
(28 kPad)
<
Override Set
Point
>
195 psig
(1345 kPa)
125 psig
(862 kPa)
150 to 245 psig
(1034-1689 kPa)
90 to 200 psig
(620 to
1379 kPa)
High Motor
Temperature
Equip-
ment
Service1
>
200 F
(93.3 C)
150 to 200 F
(66 to 93 C)
>
Override
Set Point
+10° F
(6° C)
<
Override Set
Point
Low
Refrigerant
Temperature
(Refrigerant
Override
Delta
Temperature)
Equip-
ment
Service1
<
3° F (1.6° C)
(Above Trippoint)
2° to 5° F
(1° to 3° C)
∆
T –1° F
(0.56° C)
>
Trippoint +
Override
∆
T
+2° F (1.2° C)
High
Compressor
Lift (Surge
Prevention)
Equip-
ment
Service1
HCFC-22
HFC-134a
HCFC-22
HFC-134a
None
Within Lift
Limits Plus
Surge/ HGBP
Deadband
Setting
Min:
T1 — 1.5° F
(0.8° C)
P1 — 75 psid
(517 kPad)
Max:
T2 — 10° F
(5.6° C)
P2 — 170 psid
(1172 kPad)
Min:
T1 — 1.5° F
(0.8° C)
P1 — 50 psid
(345 kPad)
Max:
T2 — 10° F
(5.6° C)
P2 — 85 psid
(586 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to
1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to
1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to
1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to
1172 kPad)
Manual
Guide Vane
Target
Control
Algo-
rithm
Maint01
Automatic
0 to 100%
None
Release of
Manual
Control