Carrier 19XL User Manual
Page 386

19XL PIC LEAD/LAG TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
0, 1, 2, 3
0
Load Balance Option
Disable/Enable
Disable
Common Sensor Option
Disable/Enable
Disable
LAG Percent Capacity
25 to 75
%
50
LAG Address
1 to 236
92
LAG START Timer
2 to 60
Min
10
LAG STOP Timer
2 to 60
Min
10
PRESTART FAULT Timer
0 to 30
Min
5
STANDBY Chiller Option
Disable/Enable
Disable
STANDBY Percent Capacity
25 to 75
%
50
STANDBY Address
1 to 236
93