CCW — Counterclockwise

CW — Clockwise

Table 6 — Potentiometer Adjustment

Dial

Adjustment Range

Function

Factory Setting

Minimum
(CCW)

Maximum
(CW)

Starting Current

100%

400%

Sets initial starting current
level.

100%

Ramp Time (Adjust-
able Current Ramp)

2 seconds

30 seconds

Sets time during which cur-
rent ramps from the initial
starting level to the maxi-
mum possible current limit
setting.

15 seconds

Current Limit

100%

400%

Sets maximum starting cur-
rent.

250%

Pulse Start

0 (Off)

2 seconds

Sets duration of 400% cur-
rent pulse. Pulse is used to
break load free.

OFF

Current Trip

50%

400%

Sets running current trip.

175%

Power Saver

OFF