Table 6, Potentiometer adjustment, Table 6 — potentiometer adjustment – Carrier 19XL User Manual
Page 278

CCW — Counterclockwise
CW — Clockwise
Table 6 — Potentiometer Adjustment
Dial
Adjustment Range
Function
Factory Setting
Minimum
(CCW)
Maximum
(CW)
Starting Current
100%
400%
Sets initial starting current
level.
100%
Ramp Time (Adjust-
able Current Ramp)
2 seconds
30 seconds
Sets time during which cur-
rent ramps from the initial
starting level to the maxi-
mum possible current limit
setting.
15 seconds
Current Limit
100%
400%
Sets maximum starting cur-
rent.
250%
Pulse Start
0 (Off)
2 seconds
Sets duration of 400% cur-
rent pulse. Pulse is used to
break load free.
OFF
Current Trip
50%
400%
Sets running current trip.
175%
Power Saver
—
—
—
OFF