* During any of the tests that are not automated, an out-of-range reading will have an asterisk (*) next to

the reading and a message will be displayed.

7. Discrete Outputs

8. Pumpdown/Lockout

9. Terminate Lockout

10. Refrigerant Type

All outputs or individual outputs may be energized:
Hot gas bypass relay
Oil heater relay
Motor cooling relay
Tower fan relay
Alarm relay

When using pumpdown/lockout, observe freeze up precau-
tions when removing charge:
Instructs operator as to which valves to close and when
Starts chilled water and condenser water pumps and con-
firms flows
Monitors —

Evaporator pressure
Condenser pressure
Evaporator temperature during pumpout procedures

Turns pumps off after pumpdown
Locks out compressor

Starts pumps and monitors flows
Instructs operator as to which values to open and when
Monitors —

Evaporator pressure
Condenser pressure
Evaporator temperature during charging process

Terminates compressor lockout

Sets refrigerant type used:
HCFC-22 or HFC-134a.
NOTE: Be sure to ATTACH TO LOCAL DEVICE after
changing refrigerant type. See

Figure 16

.