I. normal run overrides active (alerts), Table 10i — normal run overrides active (alerts) – Carrier 19XL User Manual

Page 292

background image

* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure,

voltage, etc., at which the control tripped.

Table 10I — Normal Run Overrides Active (Alerts)

Primary Message

Secondary Message

Alarm Message/Primary
Cause

Additional Cause/
Remedy

Run Capacity Lim-
ited

High Condenser Pres-
sure

CRP [VALUE]* exceeded limit of
[LIMIT]*. Condenser pressure
override.

See Capacity Over-
rides,

Table 4

. Correct

operating condition,
modify setpoint, or
release override.

Run Capacity Lim-
ited

High Motor Temperature

MTRW [VALUE]* exceeded limit of
[LIMIT]*. Motor temperature over-
ride.

Run Capacity Lim-
ited

Low Evap Refrig Temp

ERT [VALUE]* exceeded limit of
[LIMIT]*. Check refrigerant charge
level.

Run Capacity Lim-
ited

High Compressor Lift

Surge Prevention Override; lift too
high for compressor.

Run Capacity Lim-
ited

Manual Guide Vane Tar-
get

GV TRG Run Capacity Limited:
Manual guide vane target.