Installation

1. Verify if the existing PSIO module is defective, by using the procedure described in the

Troubleshooting Guide

section, and

Control Modules

section. Do not select the Attach to

Network Device table if the LID displays communication failure.

2. Data regarding the PSIO configuration should have been recorded and saved. This data will

have to be reconfigured into the LID. If this data is not available, follow the procedures

described in the

Set Up Machine Control Configuration

section.

If a CCN Building Supervisor or Service Tool is present, the module configuration should

have already been uploaded into memory; then, when the new module is installed, the con-

figuration can be downloaded from the computer.

Any communication wires from other machines or CCN modules should be disconnected to

prevent the new PSIO module from uploading incorrect run hours into memory.

3. Check that all power to the unit is off. Carefully disconnect all wires from the defective

module by unplugging the 6 connectors. It is not necessary to remove any of the individual

wires from the connectors.

4. Remove defective PSIO by removing its mounting screw with a long-shaft Phillips

screwdriver, and removing the module from the control box. Save the screw for later use.

The green ground wire is held in place with the module mounting screw.

5. Package the defective module in the carton of the new module for return to Carrier.