beautypg.com

Voltage drop, Check sensor accuracy – Carrier 19XL User Manual

Page 221

background image

a digital ohmmeter. The resistance and corresponding temperature is listed in

Table 11A

or

Table 11B

. Check the resistance of both wires to ground. This resistance should be infinite.

Voltage Drop

Using a digital voltmeter, the voltage drop across any energized sensor can be measured

while the control is energized.

Table 11A

or

Table 11B

lists the relationship between

temperature and sensor voltage drop (volts dc measured across the energized sensor).

Exercise care when measuring voltage to prevent damage to the sensor leads, connector

plugs, and modules. Sensors should also be checked at the sensor plugs. Check the sensor

wire at the sensor for 5 vdc if the control is powered.

Check Sensor Accuracy

Place the sensor in a medium of a known temperature and compare that temperature to the

measured reading. The thermometer used to determine the temperature of the medium should

be of laboratory quality with 0.5° F (.25° C) graduations. The sensor in question should be

accurate to within 2° F (1.2° C).

CAUTION

CAUTION

!

Relieve all refrigerant pressure or drain the water prior to replacing the tempera-
ture sensors.