A. shutdown with on/off/reset-off, Table 10a — shutdown with on/off/reset-off – Carrier 19XL User Manual
Page 283

Legend For Table 10, A - N
1CR AUX
—
Compressor Start Contact
OILPD
—
Oil Pressure
CA P
—
Compressor Current
OILT
—
Oil Sump Temperature
CDFL
—
Condenser Water Flow
PIC
—
Product Integrated Control
CHIL S S
—
Chiller Start/Stop
PRS TRIP
—
Pressure Trip Contact
CMPD
—
Discharge Temperature
PSIO
—
Processor Sensor Input/Output Module
CRP
—
Condenser Pressure
RLA
—
Rated Load Amps
ERT
—
Evaporator Refrigerant Temperature
RUN AUX
—
Compressor Run Contact
EVFL
—
Chilled Water Flow
SPR PL
—
Spare Protective Limit Input
GV TRG
—
Target Guide Vane Position
SMM
—
Starter Management Module
LID
—
Local Interface Device
STR FLT
—
Starter Fault
MTRB
—
Bearing Temperature
TXV
—
Thermostatic Expansion Valve
MTRW
—
Motor Winding Temperature
V P
—
Line Voltage: Percent
V REF
—
Voltage Reference
Table 10A — Shutdown with On/Off/Reset-Off
Primary Message
Secondary Message
Probable Cause/Remedy
Manually Stopped —
Press
CCN or Local to Start
PIC in OFF mode, press the CCN or
local softkey to start unit.
Terminate Pumpdown
Mode
To Select CCN or Local
Enter the Control Test table and
select Terminate Lockout to unlock
compressor.
Shutdown In Progress
Compressor Unloading
Machine unloading before shutdown
due to Soft Stop feature.
Shutdown In Progress
Compressor Deenergized
Machine compressor is being com-
manded to stop. Water pumps are
deenergized within one minute.
Ice Build
Operation Complete
Machine shutdown from Ice Build
operation.