A. shutdown with on/off/reset-off, Table 10a — shutdown with on/off/reset-off – Carrier 19XL User Manual

Page 283

background image

Legend For Table 10, A - N

1CR AUX

Compressor Start Contact

OILPD

Oil Pressure

CA P

Compressor Current

OILT

Oil Sump Temperature

CDFL

Condenser Water Flow

PIC

Product Integrated Control

CHIL S S

Chiller Start/Stop

PRS TRIP

Pressure Trip Contact

CMPD

Discharge Temperature

PSIO

Processor Sensor Input/Output Module

CRP

Condenser Pressure

RLA

Rated Load Amps

ERT

Evaporator Refrigerant Temperature

RUN AUX

Compressor Run Contact

EVFL

Chilled Water Flow

SPR PL

Spare Protective Limit Input

GV TRG

Target Guide Vane Position

SMM

Starter Management Module

LID

Local Interface Device

STR FLT

Starter Fault

MTRB

Bearing Temperature

TXV

Thermostatic Expansion Valve

MTRW

Motor Winding Temperature

V P

Line Voltage: Percent

V REF

Voltage Reference

Table 10A — Shutdown with On/Off/Reset-Off

Primary Message

Secondary Message

Probable Cause/Remedy

Manually Stopped —
Press

CCN or Local to Start

PIC in OFF mode, press the CCN or
local softkey to start unit.

Terminate Pumpdown
Mode

To Select CCN or Local

Enter the Control Test table and
select Terminate Lockout to unlock
compressor.

Shutdown In Progress

Compressor Unloading

Machine unloading before shutdown
due to Soft Stop feature.

Shutdown In Progress

Compressor Deenergized

Machine compressor is being com-
manded to stop. Water pumps are
deenergized within one minute.

Ice Build

Operation Complete

Machine shutdown from Ice Build
operation.