If, after configuring a value for these points, surge prevention is operating too soon or too late

for conditions, these parameters should be changed by the operator.

Example of configuration: Machine operating parameters

Refrigerant used: HCFC-22

Estimated Minimum Load Conditions:

44 F (6.7 C) LCW

45.5 F (7.5 C) EWC

43 F (6.1 C) Suction Temperature

70 F (21.1 C) Condensing Temperature

Estimated Maximum Load Conditions:

44 F (6.7 C) LCW

54 F (12.2 C) ECW

42 F (5.6 C) Suction Temperature

98 F (36.7 C) Condensing Temperature