Starting Current

The torque required to start a machine (initial torque) varies from one application to another.

Starting current may be adjusted to match the initial motor torque of the application. The starting

current value is adjustable from 100% to 400% FLA and is factory set at 100%. If quick

acceleration is desired, set the starting current at a higher level.

CAUTION

CAUTION

!

Do not adjust any potentiometer beyond its stops. This type of adjustment will
result in damage to the potentiometer.

Click here for Table 6 — Potentiometer Adjustment

Click here for Figure 32 — Typical Potentiometer Adjustment

Click here for Figure 33 — Typical Cutler-Hammer® Solid State Starter