19XL PIC CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
RESET TYPE 1
Degrees Reset at 20 mA
–30 to 30
(–17 to 17)
DEG F
(DEG C)
10
(6)
RESET TYPE 2
Remote Temp (No Reset)
–40 to 245
(–40 to 118)
DEG F
(DEC C)
85
(29)
Remote Temp (Full Reset)
–40 to 245
(–40 to 118)
DEG F
(DEG C)
65
(18)
Degrees Reset
–30 to 30
(–17 to 17)
DEG F
(DEG C)
10
(6)
RESET TYPE 3
CHW Temp (No Reset)
0 to 15
(0 to 8)
DEG F
(DEG C)
10
(6)
CHW Temp (Full Reset)
0 to 15
(0 to 8)
DEG F
(DEG C)
0
(0)
Degrees Reset
–30 to 30
(–17 to 17)
DEG F
(DEG C)
5
(3)
Select/Enable Reset Type
0 to 3
0
ECW Control Option
Disable/Enable
Disable
Demand Limit at 20 mA
40 to 100
%
40
20 mA Demand Limit Option
Disable/Enable
Disable
Auto Restart Option
Disable/Enable
Disable
Remote Contacts Option
Disable/Enable
Disable
Temp Pulldown Deg/Min
2 to 10
3
Load Pulldown %/Min
5 to 20
10
Select Ramp Type:
Temp=0/Load=1
0/1
1
Loadshed Group Number
0 to 99
0
Loadshed Demand Delta
0 to 60
%
20
Maximum Loadshed Time
0 to 120
Min
60
CCN Occupancy Config:
Schedule Number
3 to 99
3
CCN Occupancy Config:
Broadcast Option
Disable/Enable
Disable
ICE BUILD Option
Disable/Enable
Disable
ICE BUILD TERMINATION:
0 =Temp, 1 =Contacts, 2 =Both
0, 1, 2
0
ICE BUILD RECYCLE Option
Disable/Enable
Disable
CL-5