To Read Refrigerant Pressures

during pumpout or leak testing:

1. The LID display on the machine control center is suitable for determining refrigerant-side

pressures and low (soft) vacuum. For evacuation or dehydration measurement, use a

quality vacuum indicator or manometer to ensure the desired range and accuracy. This can

be placed on the Schrader connections on each vessel (

Figure 8

) by removing the pressure

transducer.

2. To determine storage tank pressure, a 30 in.-0-400 psi (-101- 0-2760 kPa) gage is attached

to the vessel.

3. Refer to

Figure 27

,

Figure 28

, and

Figure 37

for valve locations and numbers.

Machines with Storage Tanks

If the machine has isolation valves, leave them open for the following procedures. The letter

‘‘C’’ describes a closed valve. Valves 9 and 10 on the storage tank are always closed. See

Figure 16

,

Figure 17

,

Figure 27

, and

Figure 28

.

CAUTION

CAUTION

!

Transfer, addition, or removal of refrigerant in spring-isolated machines may
place severe stress on external piping if springs have not been blocked in both