Solid-state starters – Carrier 19XL User Manual
Page 241

14. Restore chiller to normal operation, calibrate motor amps.
Solid-State Starters
Troubleshooting guides and information pertaining to the operation of the solid-state starter
may be found in
Attempt to solve the problem by using the following preliminary checks before consulting the
troubleshooting tables.
When the power is off:
•
Inspect for physical damage and signs of arcing, overheating, etc.
•
Is the wiring to the starter correct?
•
Are all connections in the starter tight?
•
Is the current feedback resistor properly adjusted and installed?
•
Is a heater coil installed in each leg of the motor?
•
Is the control transformer fuse blown?
•
Is the motor connected to the starter?
Testing Silicon Control Rectifiers in Benshaw, Inc. Solid-State Starters
If a silicon control rectifier (SCR) is suspected of being defective, use the following procedure
as part of a general troubleshooting guide.