Table 10H — Normal Run with Reset, Temperature, or Demand

Primary Message

Secondary Message

Probable Cause/Remedy

Running — Reset Active

4-20MA Signal

Reset program active based upon Config table
setup.

Running — Reset Active

Remote Sensor Control

Running — Reset Active

CHW Temp Difference

Running — Temp
Control

Leaving Chilled Water

Default method of temperature control.

Running — Temp
Control

Entering Chilled Water

ECW control activated on Config table.

Running — Temp
Control

Temperature Ramp Loading

Ramp loading in effect. Use Service1 table to
modify.

Running — Demand
Limited

By Demand Ramp Loading

Ramp loading in effect. Use Service1 table to
modify.

Running — Demand
Limited

By Local Demand Setpoint

Demand limit setpoint is

<

actual demand.

Running — Demand
Limited

By 4-20MA Signal

Demand limit is active based on Config table
setup.

Running — Demand
Limited

By CCN Signal

Running — Demand
Limited

By LoadShed/Redline

Running — Temp
Control

Hot Gas Bypass

Hot Gas Bypass is energized. See

Surge Preven-

tion

in the Control section.

Running — Demand
Limited

By Local Signal

Active demand limit manually overridden or
Status01 table.

Running — Temp
Control

Ice Build Mode

Machine is running under Ice Build temperature
control.