Manual Operation of the Guide Vanes

Manual operation of the guide vanes is helpful to establish a steady motor current for

calibration of the motor amps value.

In order to manually operate the guide vanes, it is necessary to override the

TARGET GUIDE

VANE POSITION

value which is accessed on the Status01 table. Manual control is indicated by

the word ‘‘SUPVSR!’’ flashing after the target value position. Manual control is also indicated on

the default screen on the run status line.

1. Access the Status01 table and look at the target guide vane position (

Figure 16

). If the

compressor is off, the value will read zero.

2. Move the highlight bar to the

TARGET GUIDE VANE POSITION

line and press the

SELECT softkey.

3. Press ENTER to override the automatic target. The screen will now read a value of zero,

and the word ‘‘SUPVSR!’’ will flash.

4. Press the SELECT softkey, and0 then press RELEASE softkey to release the vanes to

AUTOMATIC mode. After a few seconds the ‘‘SUPVSR!’’ will disappear.

Dry Run to Test Start-Up Sequence

1. Disengage the main motor disconnect on the starter front panel. This should only

disconnect the motor power. Power to the controls, oil pump, and starter control circuit

should still be energized.