light and the fault indicator (FLT) is a flashing red light, the a motor overload trip is
approaching. When the FLT LED is a solid red light and the SYST RDY LED is a flashing
green light, a motor overload trip has occurred. When the FLT LED is a solid red light
and the SYST RDY LED is a solid green light, the overload has tripped because of a
phase unbalance.
Click here for Figure 50 — Cutler-Hammer® Terminal Functions
Click here for Figure 51 — Solid-State Starter, General Operation Troubleshooting
Guide (Typical)
Click here for Table 12 — Benshaw, Inc. Solid-State Starter Troubleshooting Guide