System Ready (SYST RDY)

— This light-emitting diode (LED) provides a visual indication

that the EPR is functioning.

Trip Time Potentiometer

— The Trip Time potentiometer has 50 selectable overload trip

classes ranging from 1 to 50 seconds.

Reset Time Potentiometer

— The Reset Time potentiometer has 5 to 120 minutes of motor

cooling reset.

Full Load Amperes (FLA)

— The FLA potentiometer is adjustable from 1 to 1,500 amps,

based on overload frame size.

Trip LED

— The Trip LED provides a visual indication that the EPR has detected an overload

condition and tripped.

Fault (FLT) LED

— The FLT LED is an indicator light.

Reset Button

— The RESET button allows for the manual reset of the EPR.

Trip, Common (COM), and FLA Test Terminals

— The Trip, COM, and FLA test terminals

provide for Digital Voltmeter (DVM) calibration.

Terminal 1 (TB1)

— Terminal 1 is the 120 vac connection to power the EPR.

Terminal 4 (TB4)

— Terminal 4 is the normally closed, electronically isolated EPR contact for

overload trip.

Note: When the System Ready (SYST RDY) LED is a steady green light, no fault has been

found in the solid-state starter operation. When the SYST RDY LED is a steady green