Ramp Loading Control

The ramp loading control slows down the rate at which the compressor loads up. This control

can prevent the compressor from loading up during the short period of time when the machine

is started, and the chilled water loop has to be brought down to normal design conditions. This

helps reduce electrical demand charges by slowly bringing the chilled water to control point.

However, the total power draw during this period remains almost unchanged.

There are 2 methods of ramp loading with the PIC. Ramp loading can be based on chilled

water temperature or on motor load.

1. Temperature ramp loading limits the rate at which either leaving chilled water or entering

chilled water temperature decreases by an operator-configured rate. The lowest

temperature ramp table will be used the first time the machine is started (at

commissioning). The lowest temperature ramp rate will also be used if machine power has

been off for 3 hours or more (even if the motor ramp load is selected).

2. Motor load ramp loading limits the rate at which the compressor motor current or

compressor motor load increases by an operator-configured rate.

The

TEMP

(

Temperature

)

PULLDOWN, LOAD PULL DOWN

, and

SELECT RAMP TYPE

may be viewed/modified on the LID Equipment Configuration table, Config table (see

Table 2

).

Motor load is the default type.