beautypg.com

Inspect the heat exchanger tubes, Cooler, Condenser – Carrier 19XL User Manual

Page 212

background image

symptom appears, contact an experienced and responsible service organization for assistance.

Inspect the Heat Exchanger Tubes

Cooler

Inspect and clean the cooler tubes at the end of the first operating season. Because these

tubes have internal ridges, a rotary-type tube cleaning system is necessary to fully clean the

tubes. Upon inspection, the tube condition will determine the scheduled frequency for cleaning,

and will indicate whether water treatment is adequate in the chilled water/brine circuit. Inspect

the entering and leaving chilled water temperature sensors for signs of corrosion or scale.

Replace the sensor if corroded or remove any scale if found.

Condenser

Since this water circuit is usually an open-type system, the tubes may be subject to

contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least

once per year, and more often if the water is contaminated. Inspect the entering and leaving

condenser water sensors for signs of corrosion or scale. Replace the sensor if corroded or

remove any scale if found.

Higher than normal condenser pressures, together with the inability to reach full refrigeration

load, usually indicate dirty tubes or air in the machine. If the refrigeration log indicates a rise

above normal condenser pressures, check the condenser refrigerant temperature against the