Chilled water recycle mode – Carrier 19XL User Manual

Page 122

background image

if the machine shuts down due to low refrigerant temperature, the chilled water pump
will stay running until the

LEAVING CHILLED WATER

is greater than

CONTROL

POINT

, plus 5° F (3° C)

Automatic Soft Stop Amps Threshold (PSIO Software Version 09 and
Higher)

The SOFT STOP AMPS THRESHOLD closes the guide vanes of the compressor

automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is

deenergized.

If the STOP button is pressed, the guide vanes close to a preset amperage percent or until

the guide vane is less than 2% open. The compressor will then shut off.

If the machine enters an alarm state or if the compressor enters a RECYCLE mode, the

compressor will be deenergized immediately.

To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the

SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut

down. The default setting is 100% amps (no Soft Stop).

When the SOFT STOP AMPS THRESHOLD is being applied, a status message

‘‘SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING’’ is shown.

Chilled Water Recycle Mode

The machine may cycle off and wait until the load increases to restart again when the