Shunt trip, Default screen freeze, Motor cooling control – Carrier 19XL User Manual

Page 81

background image

Shunt Trip

The shunt trip function of the PIC is a safety trip. The shunt trip is wired from an output on the

SMM to the motor circuit breaker. If the PIC tries to shut down the compressor through normal

shutdown procedure but is unsuccessful for 30 seconds, the shunt trip output is energized and

causes the circuit breaker to trip off. If ground fault protection has been applied to the starter,

the ground fault trip will also energize the shunt trip to trip the circuit breaker.

Default Screen Freeze

Whenever an alarm occurs, the LID default screen will freeze displaying the condition of the

machine at the time of alarm. Knowledge of the operating state of the chiller at the time an

alarm occurs is useful when troubleshooting. Current machine information can be viewed on the

Status tables. Once all existing alarms are cleared (by pressing the RESET softkey), the default

LID will return normal operation.

Motor Cooling Control

Motor temperature is reduced by refrigerant entering the motor shell and evaporating. The

refrigerant is regulated by the motor cooling relay. This relay will energize when the compressor

is running and motor temperature is above 125 F (51.7 C). The relay will close when motor

temperature is below 100 F (37.8 C). Note that there is always a minimum flow of refrigerant

when the compressor is operating for motor cooling; the relay only controls additional

refrigerant to the motor.