Note: Unit-mounted starters do not have to be megohm tested.

10. Tighten up all wiring connections to the plugs on the SMM, 8-input, and PSIO modules.

11. Ensure that the voltage selector switch inside the power panel is switched to the incoming

voltage rating.

12. On machines with freestanding starters, inspect the power panel to ensure that the

contractor has fed the wires into the bottom of the panel. Wiring into the top of the panel can

cause debris to fall into the contactors. Clean and inspect the contactors if this has

occurred.

Carrier Comfort Network Interface

The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by

the electrical contractor. It consists of shielded, 3-conductor cable with drain wire.

The system elements are connected to the communication bus in a daisy chain

arrangement. The positive pin of each system element communication connector must be wired

to the positive pins of the system element on either side of it; the negative pins must be wired to

the negative pins; the signal ground pins must be wired to signal ground pins.

To attach the CCN communication bus wiring, refer to the certified drawings and wiring

diagrams. The wire is inserted into the CCN communications plug (COMM1) on the PSIO

module. This plug also is referred to as J5.

Note: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded,