High altitude locations – Carrier 19XL User Manual

Page 164

background image

Check Optional Pumpout System Controls and Compressor

Controls include an on/off switch, a 3-amp fuse, the compressor overloads, an internal

thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure

cutout is factory set to open at 220 ± 5 psig (1250 ± 34 kPa), and automatically reset at 185

+0,–7 (1280 +0,–48 kPa) with HCFC-22. HFC-134a units open at 161 psig (1110 kPa) and

reset at 130 psig (896 kPa). Check that the water-cooled condenser has been connected.

Loosen the compressor holddown bolts to allow free spring travel. Open the compressor

suction and discharge service valves. Check that oil is visible in the compressor sight glass.

Add oil if necessary.

See

Pumpout and Refrigerant Transfer Procedures

and

Optional Pumpout System

Maintenance

sections, for details on transfer of refrigerant, oil specifications, etc.

High Altitude Locations

Recalibration of the pressure transducers will be necessary as the machine was initially

calibrated at sea level. Please see the calibration procedure in the

Troubleshooting Guide

section.