19XL PIC SERVICE1 TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Motor Temp Override
150 to 200
(66 to 93)
DEG F
(DEG C)
200
(93)
Cond Pressure Override
150 to 245
(1034 to 1639)
[90 to 200 (620 to 1379)]
psig
(kPa)
195
(1345)
[125 (862)]
Refrig Override Delta T
2 to 5
(1 to 3)
DEG F
(DEG C)
3
(1.6)
Chilled Medium
Water/Brine
Water
Brine Refrig Trippoint
8 to 40
(–13.3 to 4)
DEG F
(DEG C)
33
(1)
Compr Discharg Alert
125 to 200
(52 to 93)
DEG F
(DEG C)
200
(93)
Bearing Temp Alert
175 to 185
(79 to 85)
DEG F
(DEG C)
175
(79)
Water Flow Verify Time
0.5 to 5
MIN
5
Oil Press Verify Time
15 to 300
SEC
15
Water/Brine Deadband
0.5 to 2.0
(0.3 to 1.1)
DEG F
(DEG C)
1.0
(0.6)
Recycle Restart Delta T
2.0 to 10
(1.1 to 5.5)
DEG F
(DEG C)
5
(2.8)
Surge Limit/HGBP Option
Surge=0/HGBP=1
0/1
0
Surge/HGBP Delta T1
0.5 to 15
(0.3 to 8.3)
DEG F
(DEG C)
1.5
(0.8)
Surge/HGBP Delta P1
50 to 170
(345 to 1172)
[30 to 170 (206 to 1172)]
psi
(kPa)
75
(517)
[50 (345)]
Surge/HGBP Delta T2
0.5 to 15.0
(0.3 to 8.3)
DEG F
(DEG C)
10
(5.6)
Surge/HGBP Delta P2
50 to 170
(345 to 1172)
[30 to 170 (206 to 1172)]
psi
(kPa)
170
(1172)
[85 (586)]
Surge/HGBP Deadband
1 to 3
(0.6 to 1.6)
DEG F
(DEG C)
1
(0.6)
Surge Delta Percent Amps
10 to 50
%
25
Surge Time Period
1 to 5
MIN
2
Demand Limit Source
Amps=0/Load=1
0/1
0
Amps Correction Factor
1 to 8
3
NOTE: Values in [ ] indicate HFC-134a values, if this refrigerant is configured in the Control Test.
CL-7