Charge Refrigerant into Machine

The standard 19XL machine will have the refrigerant already charged in the vessels. The

19XL may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the entire

machine, and charge machine from refrigerant cylinders.

19XL Machine Equalization without Pumpout Unit

CAUTION

CAUTION

!

The transfer, addition, or removal of refrigerant in spring isolated machines may
place severe stress on external piping if springs have not been blocked in both
up and down directions.

When equalizing refrigerant pressure on the 19XL machine after service work or
during the initial machine start-up,

do not use the discharge isolation valve to

equalize

. The motor cooling isolation valve or charging hose (connected between

pumpout valves on top of cooler and condenser) is to be used as the equalization
valve.

WARNING

!

WARNING