* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure,

voltage, etc., at which the control tripped.

Table 10L — Machine Alerts

Primary
Message

Secondary
Message

Alarm Message/
Primary Cause

Additional Cause/Remedy

Recycle Alert

High Amps at Shut-
down

High Amps at Recycle:
Check guide vane drive.

Check that guide vanes are closing. Check
motor amps correction calibration is cor-
rect. Check actuator for proper operation.

Sensor Fault
Alert

Leaving Cond Water
Temp

Sensor Fault: Check
leaving condenser water
sensor.

Check sensor. See sensor test procedure.

Sensor Fault
Alert

Entering Cond Water
Temp

Sensor Fault: Check
entering condenser
water sensor.

Low Oil
Pressure Alert

Check Oil Filter

Low Oil Pressure Alert:
Check oil.

Check oil filter. Check for improper oil level
or temperature.

AutoRestart
Pending

Power Loss

V P Power Loss:
Check voltage supply.

Check power supply if there are excessive
compressor starts occurring.

AutoRestart
Pending

Low Line Voltage

V P [VALUE] exceeded
limit of [LIMIT*]. Check
voltage supply.

AutoRestart
Pending

High Line Voltage

V P [VALUE] exceeded
limit of [LIMIT*]. Check
voltage supply.

Sensor Alert

High Discharge Temp

CMPD [VALUE]
exceeded limit of
[LIMIT*]. Check dis-
charge temperature.

Discharge temperature exceeded the alert
threshold. Check entering condenser water
temperature.

Sensor Alert

High Bearing Tempera-
ture

MTRB [VALUE]
exceeded limit of
[LIMIT*]. Check thrust
bearing temperature.

Thrust bearing temperature exceeded the
alert threshold. Check for closed valves,
improper oil level or temperatures.

Condenser
Pressure Alert

Pump Relay Energized

CRP High Condenser
Pressure [LIMIT*].
Pump energized to
reduce pressure.

Check ambient conditions. Check con-
denser pressure for accuracy.

Recycle Alert

Excessive Recycle
Starts

Excessive recycle
starts.

The machine load is too small to keep the
machine on line and there have been more
than 5 restarts in 4 hours. Increase
machine load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T.