spare protective limits input channel in place of the factory-installed jumper. (Wire multiple

inputs in series.) The opening of any contact will result in a safety shutdown and LID display.

Refer to the certified drawings for safety contact ratings.

Analog temperature sensors may also be added to the options modules, if installed. These

may be programmed to cause an alert on the CCN network, but will not shut the machine down.

Spare Alarm Contacts

Two spare sets of alarm contacts are provided within the starter. The contact ratings are

provided in the certified drawings. The contacts are located on terminal strip TB6, terminals 5A

and 5B, and terminals 5C and 5D.

Condenser Pump Control

The machine will monitor the

CONDENSER PRESSURE

and may turn on this pump if the

pressure becomes too high whenever the compressor is shut down.

CONDENSER

PRESSURE OVERRIDE

is used to determine this pressure point. This value is found on the

Equipment Service1 LID table and has a default value (

Table 4

). If the

CONDENSER

PRESSURE

is greater than or equal to the

CONDENSER PRESSURE OVERRIDE

, and the

ENTERING CONDENSER WATER TEMP

(

Temperature

) is less than 115 F (46 C), then the

condenser pump will energize to try to decrease the pressure. The pump will turn off when the

condenser pressure is less than the pressure override less 5 psi (34 kPa), or the

CONDENSER

REFRIG (Refrigerant) TEMP

is within 3° F (2° C) of the

ENTERING CONDENSER WATER

temperature.