Carrier 19XL User Manual

Page 300

background image

SMM
Communications
Failure

Check that PSIO communication plugs are connected correctly. Check SMM com-
munication plug. Check for proper SMM power supply. See

Control Modules

sec-

tion.

High Oil
Temperature
While Running

Check for proper oil level (too much oil). Check that TXV valve is operating prop-
erly.

Blank LID Screen

Increase contrast potentiometer. See

Figure 42

. Check red LED on LID for proper

operation, (power supply). If LED is blinking, but green LED’s are not, replace LID
module, (memory failure).

‘‘Communications
Failure’’
Highlighted
Message At
Bottom of LID
Screen

LID is not properly addressed to the PSIO. Make sure that ‘‘Attach to Network
Device,’’ ‘‘Local Device’’ is set to read the PSIO address. Check LED’s on PSIO. Is
red LED operating properly? Are green LED’s blinking? See control module trou-
bleshooting section.

Controls Test
Disabled

Press the ‘‘Stop’’ pushbutton. The PIC must be in the OFF mode for the controls
test to operate. Clear all alarms. Check line voltage percent on Status01 screen.
The percent must be within 90% to 110%. Check voltage input to SMM, calibrate
starter voltage potentiometer for accuracy.

Vanes Will Not
Open In Control
Test

Low pressure alarm is active. Put machine into pumpdown mode or equalize pres-
sure. Check guide vane actuator wiring.

Oil Pump Does
Not Run

Check oil pump voltage supply. Cooler vessel pressure under vacuum. Pressurize
vessel. Check temperature overload cutout switch.

Table 10N — Other Problems/Malfunctions (Continued)

Description/
Malfunction

Probable Cause/Remedy