beautypg.com

B. timing out or timed out, Table 10b — timing out or timed out – Carrier 19XL User Manual

Page 284

background image

Table 10B — Timing Out or Timed Out

Primary Message

Secondary Message

Probable Cause/Remedy

Ready To Start In XX Min

Unoccupied Mode

Time schedule for PIC is unoccupied. Machines will start
only when occupied.

Ready To Start In XX Min

Remote Contacts Open

Remote contacts have stopped machine. Close contacts to
start.

Ready To Start In XX Min

Stop Command In
Effect

Chiller START/STOP on Status01 manually forced to stop.
Release value to start.

Ready To Start In XX Min

Recycle Restart Pend-
ing

Machine in recycle mode.

Ready To Start

Unoccupied Mode

Time schedule for PIC is UNOCCUPIED. Machine will start
when occupied. Make sure the time and date have been
set on the Service menu.

Ready To Start

Remote Contacts Open

Remote contacts have stopped machine. Close contacts to
start.

Ready To Start

Stop Command In
Effect

Chiller START/STOP on Status01 manually forced to stop.
Release value to start.

Ready To Start In XX Min

Remote Contacts
Closed

Machine timer counting down unit. Ready for start.

Ready To Start In XX Min

Occupied Mode

Machine timer counting down unit. Ready for start.

Ready To Start

Remote Contacts
Closed

Machine timers complete, unit start will commence.

Ready To Start

Occupied Mode

Machine timers complete, unit start will commence.

Startup Inhibited

Loadshed In Effect

CCN loadshed module commanding chiller to stop.

Ready To Start In XX Min

Start Command In
Effect

Chiller START/STOP on Status01 has been manually
forced to start. Machine will start regardless of time sched-
ule or remote contact status.