Example 12 — maintenance (maint03) display screen – Carrier 19XL User Manual

Page 266

background image

Example 12 — Maintenance (Maint03) Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT.

5. Scroll down to highlight MAINT03.

6. Press SELECT.

Note: Override is not supported on this maintenance screen. Only values with capital letter reference point

names are variables available for read operation.

Table 2, Example 12 — Maintenance (Maint03) Display Screen

Description

Range/Status

Units

Reference Point Name

SURGE/HGBP ACTIVE?
Active Delta P
Active Delta T
Calculated Delta T
Surge Protection Counts

NO/YES
0-200 (0-1379)
0-200 (0-111)
0-200 (0-111)
0-12

PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)

dp a
dt a
dt c
spc