Manning-strickler, Auto calculation – ADS Environmental Services FlowShark Pulse QR 775004 A1 User Manual
Page 161

Parameter Settings
8-71
Manning-Strickler
The user can change the Manning-Strickler coefficient and slope values used to
populate the internal Manning-Strickler table manually or allow them to adjust
automatically by setting the auto calculation function to yes (Refer to Auto
Calculation on page 8-71).
Figure 8-119
Auto Calculation
Selecting automatic YES from the auto calibration menu automatically updates the
Manning-Strickler table based on the last valid velocity value before depth drops
below h-critical. Selecting automatic NO prevents set values (including v-critical)
from changing, regardless of subsequent measurements.
Use the ALT button to toggle between YES and NO.
Running simulations through FlowShark Pulse outputs will impact
controlled facility equipment that does not have security measures
in place!
Simulations should be executed only by knowledgeable personnel.
Due to the extremely high risk of danger and unpredictable
consequences that may arise from incorrect or faulty simulations,
ADS is not responsible for any possible injury to persons or
damage to property that may occur.